Descripción
Flame detector with dual infrared sensor FF746
The FF746 is a dual infrared flame detector, mounted on a flammable housing. This detector has an excellent response that gives high immunity to foreign sources that may interfere with you. The new technology of its microprocessor allows you to work with different levels of flame intensity and allows you to operate normally in adverse conditions, such as through smoke, vapors, dust, etc.. The sensitivity of the detector can be adjusted in accordance with EN54-10.
How is the installation and maintenance of the flame detector with dual infrared sensor Flame detector with dual infrared sensor FF746?
The detector can be wired with two wires as a conventional system, through 4-20mA current loop or through voltage-free contacts. It can work with or without alarm interlocking. You can remotely activate the auto-test utility. An adjustable stainless steel bracket can optionally be supplied. The detector tolerates vibrations, and the wind does not affect its performance at all. Theinfrared sensor has an excellent response that even allow you to work through crystals or windows. Special test equipment is available for fine and precise adjustment of this type of detector. This test equipment also allows for operational testing.
How much does the flame detector with dual-infrared sensor flame detector with dual infrared sensor FF746 reduce false alarms?
Most infrared detectors respond to light with a wavelength of about 4.3µm, corresponding to the flames of most hydrocarbons. Thanks to its extended response, between 1.0 and 2.7om, this detector can respond to most flames even flashing. It can even detect flames not visible to thehuman eye, such as hydrogen flames. The FF746 detector also responds to wavelengths adjacent to those described, so they can discriminate between real flames and spurious sources of sparks or flashes. The combination of the filters that the detector hasand the processing of the signal that is performed, make this detector can be used without any risk of false alarms in difficult situations, such as due to flashes of sunlight.
Features of the FF746 Infrared Dual Sensor Flame Detector
- Dual-tech infrared detector
- Specials for working in difficult conditions
- IP66 housing
- Explosion-proof housing
- Low current consumption
- Current loop and contact outputs
- Works with or without interlocking
- Adjustable sensitivity
- Tolerates dirty environments
- Auto-test utility
- Microprocessor controlled
- Immune to false alarms (sparks, flashes, etc.)
- According to EN54-10
Operating voltage | 14 to 30 VDC |
Net weight | 2.5kg |
Operating temperature | -10 up to + 55oC |
Storage temperature | -20 up to + 65oC |
Relative humidity | 95% max. non-condensing |
Environment | Exd, Interior |
IP rating | IP66 |
Supply voltage | 14 – 30 VDC |
Supply current | 3/9, 4/8/14, 4-20, 8-20 mA |
Relay contact ratings | 1 A to 30 VDC (resistive load) |
Field of view | 90 min. cone |
Spectral Response (IR) | 1 to 2.7 m |
IEC marking | EEx d IIC T6 |