Conventional fire plant. CLVR
COFEM’s conventional fire detection plants allow us to install a manual or automatic fire protection system in places that require basic fire safety protection.
These types of power plants are very economical and give us a solution to the basic alarm detection needs.
You can choose models of 2 zones, 4 zones, 8 zones and 12 zones.
Models of CLVR fire plants
- CLVR 02Z – 2-zone central
- CLVR 04Z – 4-zone central
- CLVR 08Z – 8-zone central
- CLVR 12Z – 12-zone central
- CLVR 02ZMDB – 2-zone central with Modbus protocol
- CLVR 04ZMDB – 4-zone central with Modbus protocol
- CLVR 08ZMDB – 8-zone central with Modbus protocol
- CLVR 12ZMDB – 12-zone central with Modbus protocol
Features of Cofem’s CLVR fire plants
- It has two siren outputs monitored and protected each by a fuse.
- It has an immediate alarm output through a normally open or closed contact
- A fault outlet through a normally open or closed contact
- 2 30 V auxiliary outputs protected by a fuse for external power supply of electromagnets, sirens, etc.
- It has a test mode for plant maintenance and equipment testing.
- Allows the configuration of open line thresholds, detector alarm and pushbutton alarm to adjust them with other detectors.
- It also allows you to configure the last zone as input to an external system to indicate faults.
- It has space for 2 7Ah batteries that are not included.
- Certified according to UNE EN-52-2 and UNE EN-54-4 with CE marking
Cofem CLVR Conventional Fire Central Technical Specifications:
Supply voltage |
110 / 230V at 50 /60 Hz | Final line resistance |
4K7 |
Output voltage |
21 V Nominal | Siren output voltage |
30 V/DC |
Maximum consumption |
70 V to 230 V/AC | Fault exit |
Yes, dry contact |
Batteries |
2 x 12 V to 7 Ah | Environmental conditions |
-10oC + 50oC |
Maximum output current 30V |
0.75 / 1.50A | Dimensions |
363 x 331 x 96 mm |
Battery charger |
500 mA 27 V/DC 20o | Weight (without batteries) |
4.3 Kg |
Items by zone |
32 | Regulations |
EN-54-2, EN54-4, EN12094-1 |
Power supply |
2.2 A | Fuse output siren S1 |
1A / 1.85A |
Maximum current per zone |
2 mA at rest | Fuse output siren S1 | 1A / 0.75A |