Thermal detectors are typically used in rooms where the temperature can be expected to rise rapidly in the event of a fire, or in places where smoke detectors cannot be used. The 6000 series is created for use in areas of high humidity both indoors and outdoors.
What are the fixed temperature alarm levels?
600 s series detectors on conventional fixed stemperature thermal detectors,for example they will give you an alarm within a temperature range in accordance with EN54-5:2000. The sensor element is a bimetallic switch with heat protection protection. An LEDon the detector (not available on the 6298) will light up when the detector is activated. All detectors include a remote indicator output.
The following models are available (Temperature response, class and temperature range according to EN54-5):
• 6295, 57oC, class A2 S (54 to 70oC)
• 6296, 72oC, Class B S (69 to 85oC)
• 6297, 87oC, Class C S (84 to 100oC)
• 6298, 117oC, Class E S (114 to 130oC)
How does the ip67 temp conventional weather detector detector work. 117th?
All detectors are interlocked,this means that they are not automatically restored if the temperature after the alarm drops below the alarm threshold. The detector LED and the remote connected LED will remain on until a reset is performed from the C.I.E.
How to install the conventional IP67 temp weather detector. 117th?
All electronic components are mounted in a grey housing with weather protection and equipped with the kind of connections supplied. The connection base has 3 cable inputs. Supplied with 3 clamping bushings and a silicone gasket for IP67 protection.
All detectors are equipped with three pairs of mobile conductors with female pressure connectors to connect the zone line cables (input/output) and the remote indicator.
Features of the conventional IP67 temp weather detector. 117th
- Fixed temperature alarm level
- ATEX Certificate (6295 and 6296)
- Weathering (IP67)
Current consumption | 0 mA (at rest) 6 – 30 mA (± 680 Ω) (alarm, internal resistance) |
Physical dimensions | 100 x 75 mm (x D) |
Net weight | 216g |
Color | Grey |
Operating temperature | -40 (min.) / +55 (nom.) / + 80oC (max.) |
Storage temperature | -45 up to + 70oC |
Environment | Interior, Exterior |
IP rating | IP67 |
Certification | EN54-5 |
Supply | Supply-2VDC |
Current (max) | 10 mA |
Static response temperature | 117oC |
Construction | Modified polycarbonate |
Certification | EN54: 5, CE, CPD |