COMPARTELO CON TU AMIGOS

Compartir en facebook
Compartir en whatsapp
Compartir en twitter
Compartir en email
Compartir en pinterest

Intrinsically Safe Conventional Smoke Detector SLR-E-IS(WHT)

119,50 + IVA

Intrinsically safe conventional smoke detector – SLR-E-IS(WHT) / Kilsen. WHITE photoelectric smoke detector.

Agotado

SKU DEL PRODUCTO: SLR-E-IS(WHT) Categorías , Etiqueta

*Los productos no incluyen gastos de transporte y los precios son exclusivos online.

Descripción

Intrinsically Safe Conventional Smoke Detector SLR-E-IS(WHT)

It is a WHITE photoelectric smoke detector designed for use in hazardous areas. It incorporates a remote indicator output and a removable camera for easy maintenance.

Each detector incorporates unique high-performance camera technology that eliminates the need for ionization detectors in most applications. This high-performance camera has also allowed to increase the threshold level of the detector, thus improving the signal-to-noise ratio and reducing susceptibility to false alarms.

 

Classification of hazardous areas conventional smoke detector intrinsically safe SLR-E-IS(WHT)

ATEX II 1G
II – Equipment group (Non-mining)
1 – Equipment category (for Zone 0 or 20)
G – Type of explosive atmosphere (Gas, vapours and mists)

Cenelec EEx ia IIC T5 Tamb ? 55 ‘ C
E – Compliance with European Standard
Ex – Explosion protection symbol
ia – Concept of protection (intrinsically safe)
IIC – Appliance group (gas)
T5 – Temperature Rating (100oC)
Tamb – Maximum Ambient Temperature (55oC)

 

Features intrinsically safe conventional smoke detector SLR-E-IS(WHT)

  • High-performance removable camera
  • Twin Fire LEDs allow for 360-degree display
  • Remote indicator output
  • ATEX rating according to II 1G EEx ia IIC T5 Tamb s 55oC
  • Suitable for installation in Category 1 areas (including all lower categories)
  • Approved by LPCB, VdS and GL

 

Status indication Led
User interface Leds
Compatibility Aritech, Kilsen & Ziton conventional zone interfaces
Connectivity 2-wire zone
Type of power supply Zone-fed
Operating voltage 15 to 30 VDC
Current consumption 50 A (inactive)
<50 mA (alarm)
Detection principle Optical light scattering
Surveillance Open circuit, short circuit
Length of the area Depends on the configuration of the area
Physical dimensions 100 x 38 mm (x H)
Net weight 115g
Color White
Type of Assembly Mount Base, Ceiling Mount
material Section
Vandalism No
Operating temperature -10 up to + 50oC
Storage temperature -30 up to + 70oC
Relative humidity <95% non-condensing at 40oC
Environment Interior, ES
Hazardous environment classification II 1G EEx & IIC T5 Tamb x 55oC
IP rating IP42
Compliance CE, ALCANCE, RoHS 2
Certification CENELEC / ATEX, VdS
Standards and regulation LPCB, Germanischer Lloyd