Conventional fire plant 4 – 48 zones. LONDON
CoFEM’s Londonconventional fireplant is designed for installation in harsh environmental conditions, driven electrical noises, vibrations and even magnetic disturbances.
We have models of fire plant 4 zones, 8 zones, 12 zones, 16 zones, 20 zones, 24 zones, 28 zones, 32 zones, 36 zones, 40 zones, 44 zones and 48 zones
16-bit technology and supports most conventional detectors on the market, with the following voltage configurations. Complies with UNE EN-54 part 2 and part 4.
Open line |
22.5 V to 24 V |
Surveillance status |
19 V to 22.5 V |
Detector alarm |
7 V to 16 V |
Push-button alarm |
3.5 V to 7 V |
Cross-line |
0 V to 3.5 V |
Features
- The control unit has a configuration of 12 modules of 4 zones or 4 relays, up to a limit of 48.
- Up to 32 modules can be extended with an additional chest, with the equipment limit being 128 between zones and relays.
- Supports 32 computers per zone.
- Can be configured with PC-Easy software
- Connects an external PC keyboard.
- Connecting up to 10 alarm repeaters
- 30 V auxiliary output
- Delayed siren output from 0 to 10 minutes, supervised.
- 1 alarm output as voltage-free relay
- 1 fault output as voltage-free relay
- Allows the connection of a printer.
- Batteries not included
Technical specifications
Supply voltage |
110 / 230V at 50 /60 Hz | Final line resistance | 4K7 |
Output voltage |
21 V Nominal | Siren output voltage | 24 V/DC – 2 A |
Consumption at rest |
70 mA | Fault exit |
No |
Batteries |
2 x 12 V to 7 Ah | Environmental conditions |
-10oC + 50oC |
Maximum output current 30V |
1 A | Dimensions | 418 x 324 x 150 mm |
Battery charger |
500 mA 27 V/DC 20oC | Weight (without batteries) |
5.9 Kg |
Items by zone |
32 | Regulations | EN-54-2, EN54-4 |
Power supply |
3 A | Consumption in alarm |
140 mA |
Maximum current per zone |
2 mA at rest | Power fuse |
4 A |